Back to the backflow review queue

Backflow assembly test: 4008 Ridgeview Way

Approved

Filed Aug 17, 2026 by Alex Kessler, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 17, 2026
Assembly type
PVB
Serial number
B326121
Size
3/4
Test gauge serial
G-9600
Gauge calibration date
Jul 13, 2026
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-53-01017
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4008 Ridgeview Way
Owner: Taylor Stroud
Parcel 097-53-01017