Back to the backflow review queue
Backflow assembly test: Golden Dental
ApprovedFiled May 29, 2024 by Drew Okafor, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- May 29, 2024
- Assembly type
- RP
- Serial number
- K727112
- Size
- 1 1/2
- Test gauge serial
- G-6746
- Gauge calibration date
- Feb 9, 2023
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Okafor, current on the service date
- All required fields present
- Address matches parcel 097-95-01166
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4827 Pine Knoll Ct
Owner: Lindqvist Holdings LLC
Parcel 097-95-01166