Backflow assembly test: Golden Dental

Approved

Filed Jun 10, 2025 by Quinn Ramirez, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 10, 2025
Assembly type
RP
Serial number
K727112
Size
1 1/2
Test gauge serial
G-8898
Gauge calibration date
Jan 10, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-95-01166
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.