Backflow assembly test: 113 Turkey Hill Ln

Approved

Filed Oct 28, 2026 by Alex Kessler, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 28, 2026
Assembly type
RP
Serial number
A855598
Size
3/4
Test gauge serial
G-9806
Gauge calibration date
Oct 7, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.7 psid
Relief valve opened at
3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-62-01169
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

113 Turkey Hill Ln
Owner: Avery Brandt
Parcel 097-62-01169