Backflow assembly test: 3809 Stone Gate Dr
ApprovedFiled Oct 24, 2024 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 24, 2024
- Assembly type
- PVB
- Serial number
- K766101
- Size
- 3/4
- Test gauge serial
- G-8547
- Gauge calibration date
- Aug 13, 2024
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Stroud, current on the service date
- All required fields present
- Address matches parcel 107-54-01208
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.