Backflow assembly test: Maple Leaf Medical Offices
ApprovedFiled Oct 14, 2025 by Jordan Brandt, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 14, 2025
- Assembly type
- RP
- Serial number
- Z907935
- Size
- 2
- Test gauge serial
- G-2688
- Gauge calibration date
- Feb 28, 2025
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Brandt, current on the service date
- All required fields present
- Address matches parcel 107-21-01200
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.