Back to the backflow review queue

Backflow assembly test: 8282 Spring Branch Way

Approved

Filed Feb 20, 2024 by Morgan Pruitt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 20, 2024
Assembly type
DC
Serial number
A554254
Size
1
Test gauge serial
G-4060
Gauge calibration date
Nov 18, 2023
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 107-52-01342
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8282 Spring Branch Way
Owner: Riley Danner
Parcel 107-52-01342