Backflow assembly test: 9726 Sycamore Dr

Approved

Filed May 25, 2024 by Parker Vance, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 25, 2024
Assembly type
RP
Serial number
A274774
Size
1
Test gauge serial
G-7312
Gauge calibration date
Aug 1, 2023
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 107-82-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9726 Sycamore Dr
Owner: Rowan Stroud
Parcel 107-82-01034