Backflow assembly test: 9726 Sycamore Dr
ApprovedFiled Jun 9, 2026 by Jordan Brandt, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 9, 2026
- Assembly type
- RP
- Serial number
- A274774
- Size
- 1
- Test gauge serial
- G-7971
- Gauge calibration date
- Jan 18, 2026
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Brandt, current on the service date
- All required fields present
- Address matches parcel 107-82-01034
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9726 Sycamore Dr
Owner: Rowan Stroud
Parcel 107-82-01034