Back to the backflow review queue
Backflow assembly test: 5635 Hickory Dr
Needs reviewFiled Nov 29, 2026 by Parker Fairley, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 29, 2026
- Assembly type
- RP
- Serial number
- Z501946
- Size
- 1
- Test gauge serial
- G-7639
- Gauge calibration date
- Aug 21, 2025
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 2.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 107-22-01068
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
5635 Hickory Dr
Owner: Reese Stroud
Parcel 107-22-01068