Backflow assembly test: 9875 Ridgeview Rd

Approved

Filed Jun 25, 2024 by Riley Ramirez, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jun 25, 2024
Assembly type
PVB
Serial number
Z573248
Size
3/4
Test gauge serial
G-7930
Gauge calibration date
Feb 28, 2024
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 107-81-01265
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9875 Ridgeview Rd
Owner: Jamie Ellery
Parcel 107-81-01265