Backflow assembly test: 8194 Mill Creek Trl

Approved

Filed Jul 23, 2023 by Parker Vance, Summit Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 23, 2023
Assembly type
RP
Serial number
B980857
Size
3/4
Test gauge serial
G-7950
Gauge calibration date
May 29, 2023
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 107-51-01010
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8194 Mill Creek Trl
Owner: Sam Kessler
Parcel 107-51-01010