Back to the backflow review queue

Backflow assembly test: 8194 Mill Creek Trl

Approved

Filed Jul 4, 2024 by Riley Ramirez, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jul 4, 2024
Assembly type
RP
Serial number
B980857
Size
3/4
Test gauge serial
G-8126
Gauge calibration date
Mar 9, 2024
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 107-51-01010
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8194 Mill Creek Trl
Owner: Sam Kessler
Parcel 107-51-01010