Backflow assembly test: Hilltop Market

Approved

Filed Oct 4, 2025 by Cameron Vance, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 4, 2025
Assembly type
RP
Serial number
W638459
Size
1 1/2
Test gauge serial
G-6597
Gauge calibration date
Feb 18, 2025
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Vance, current on the service date
  • All required fields present
  • Address matches parcel 107-64-01024
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.