Back to the backflow review queue

Backflow assembly test: 9339 Laurel Trl

Approved

Filed Feb 27, 2025 by Parker Vance, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Feb 27, 2025
Assembly type
RP
Serial number
Z102124
Size
1
Test gauge serial
G-6701
Gauge calibration date
Jun 16, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Vance, current on the service date
  • All required fields present
  • Address matches parcel 107-23-01153
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9339 Laurel Trl
Owner: Shawn Lindqvist
Parcel 107-23-01153