Backflow assembly test: 9228 Sycamore Way
ApprovedFiled Aug 9, 2026 by Jordan Brandt, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Aug 9, 2026
- Assembly type
- DC
- Serial number
- Z227598
- Size
- 1
- Test gauge serial
- G-5451
- Gauge calibration date
- May 6, 2026
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Brandt, current on the service date
- All required fields present
- Address matches parcel 107-74-01029
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9228 Sycamore Way
Owner: Reese Brandt
Parcel 107-74-01029