Back to the backflow review queue
Backflow assembly test: 4350 Pine Knoll Trl
ApprovedFiled Sep 17, 2024 by Riley Ramirez, Patriot Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 17, 2024
- Assembly type
- DC
- Serial number
- Z746760
- Size
- 1
- Test gauge serial
- G-3309
- Gauge calibration date
- Feb 23, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Ramirez, current on the service date
- All required fields present
- Address matches parcel 107-50-01081
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4350 Pine Knoll Trl
Owner: Sam Ellery
Parcel 107-50-01081