Backflow assembly test: 1236 Sycamore Ct

Approved

Filed Oct 8, 2026 by Avery Stroud, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 8, 2026
Assembly type
RP
Serial number
K804484
Size
1
Test gauge serial
G-9601
Gauge calibration date
Mar 22, 2026
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Stroud, current on the service date
  • All required fields present
  • Address matches parcel 107-99-01117
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.