Backflow assembly test: 2305 Laurel Way

Approved

Filed Jun 16, 2025 by Parker Fairley, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jun 16, 2025
Assembly type
RP
Serial number
W602406
Size
1
Test gauge serial
G-9530
Gauge calibration date
Nov 7, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 107-33-01031
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2305 Laurel Way
Owner: Morgan Ashby
Parcel 107-33-01031