Backflow assembly test: 1077 Orchard Trl

Approved

Filed May 12, 2026 by Jordan Brandt, Summit Backflow Testing. Filed from a phone.

Report

Date of service
May 12, 2026
Assembly type
RP
Serial number
A630752
Size
3/4
Test gauge serial
G-6055
Gauge calibration date
Aug 28, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Brandt, current on the service date
  • All required fields present
  • Address matches parcel 107-85-01296
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.