Backflow assembly test: Blue Heron Animal Hospital

Approved

Filed Jan 11, 2026 by Parker Fairley, Patriot Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 11, 2026
Assembly type
RP
Serial number
Z580768
Size
4
Test gauge serial
G-9605
Gauge calibration date
Nov 22, 2025
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 107-75-01223
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

401 Old Church Way
Owner: Ellery Holdings LLC
Parcel 107-75-01223